2022 Caterpillar Automatic Transfer Switch ATC Breaker / Contactor ATC-300+ Controller

2022 Caterpillar Automatic Transfer Switch ATC Breaker / Contactor ATC-300+ Controller

Swipe to View More

  • Year 2022
  • Make Caterpillar
  • Model Automatic Transfer Switch ATC Breaker / Contactor
2022 Caterpillar Automatic Transfer Switch ATC Breaker / Contactor ATC-300+ Controller

2022 Caterpillar Automatic Transfer Switch ATC Breaker / Contactor ATC-300+ Controller

2022 Caterpillar Automatic Transfer Switch ATC Breaker / Contactor ATC-300+ Controller

The ATC-300+ is a comprehensive and multifunctional microprocessor-based ATS controller. It is a compact and self-contained panel-mounted device that is designed to replace traditional relay and solid-state logic panels. The ATC-300+ Controller provides programmed flexibility to address the needs of any system. It operates from all system voltages between 120 to 600V, single-phase and three-phase at 50 or 60 Hz. In addition, a period of no control power is provided. The controller monitors the condition of the three-phase line-to-line voltage and frequency of Source 1 and Source 2 power sources and can be programmed for single-phase operation. The ATC-300+ Controller provides the intelligence to ensure that the ATS operates properly through a series of programmed sensing and timing functions.

THE ATC-300+ IS A COMPREHENSIVE AND MULTIFUNCTIONAL MICROPROCESSOR-BASED ATS CONTROLLER

IT IS A COMPACT AND SELF-CONTAINED PANEL-MOUNTED DEVICE THAT IS DESIGNED TO REPLACE TRADITIONAL RELAY AND SOLID-STATE LOGIC PANELS.

Features may include:
  • pre-transfer Signal Contacts 1no And 1nc
  • go To Emergency (Source 2)
  • seven Field-programmable Time Delays
  • lcd-based Display For Programming, System Diagnostic And Help Message Display
  • mimic Diagram With Source Available And Connected Led Indication
  • time-stamped History Log
  • system Test Pushbutton
  • programmable Plant Exercise (Off, Daily, 7,14 And 28 Day) Interval Selectable Run Time 0-600 Minutes No Load/load With Fail-safe
  • in-phase Transition
auxiliary Relay Contacts:
  • source 1 Present 2no And 2nc
  • source 2 Present 2no And 2nc
source 1 And Source 2 Sensing:
  • undervoltage / Underfrequency
  • overvoltage / Overfrequency
  • three-phase Rotation Protection
  • three-phase Voltage Unbalance/loss

Electric

Electrical Rating Range: 120 to 600V, single phase and three phase @ 50/60 Hz | Input Control Voltage: 65 to 145 Vac 50/60 hZ | Voltage Measurements of Utility: Source 1 VAB Source 2 VAB / Source 1 VAC Source 2 VBC / Source 1 VCA Source 2 VCA | Voltage Measurement Range: 0 to 790 VAC rms (50/60 Hz) | Voltage Measurement Accuracy: +/-2% of nominal input voltage | Frequency Measurement Range: 40 Hz to 70 Hz | Frequency Measurement Accuracy: +/- 0.1 Hz | Undervoltage Dropout: 50% to 90% of nominal voltage | Undervoltage Pickup: (Dropout +2%) to 99% of the nominal system voltage | Underfrequency Dropout Range: 90 to 97% of the nominal system frequency | Underfrequency Pickup Range: (Dropout +1 Hz) to 99% of the nominal system frequency | Overfrequency Dropout Range: 103 to 110% of the nominal system frequency | Overfrequency Pickup Range: 101% to (dropout - 1 Hz) of the nominal system frequency | Generator Start Relay: 5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load | K1, K2 Relays: 10A, 1-3 hp @ 250 Vac 10A@30 Vdc

Operational

Operating Conditions Humidity: 0 to 95% relative humidity (noncondensing)
Operating Temperature, Maximum Operating Temperature Range: -20 to 70 degree C (-4 to +158 degree F) | Storage Temperature Range: -30 to 85 degree C (-22 to +185 degree F)

Features

Features ransfer Type: Switch application dependent | Switch Type: Switch application dependent | Frequency Measurements Of: Source 1 and Source 2 | Operating Environment: Resistant to ammonia, methane, nitrogen,hydrogen and hydrocarbons | Applicable Testing: UL-recognized component Meets intent of UL 991 & UL 1008 Meets IEC 1000-4-2, 1000-4-3, 1000-4-4 | Applicable Testing Continued: 1000-4-5, 1000-4-6, 1000-4-11 CISPR 11, Class A FCC Part 15, Class A CSS 22.2-178 | Enclosure Compatibility: NEMA 1, NEMA 3R and NEMA 12 UV-resistant ATC-300+ faceplate

Product Photography