2022 Caterpillar Automatic Transfer Switch ATC Breaker / Contactor ATC-900 Controller

2022 Caterpillar Automatic Transfer Switch ATC Breaker / Contactor ATC-900 Controller

Swipe to View More

  • Year 2022
  • Make Caterpillar
  • Model Automatic Transfer Switch ATC Breaker / Contactor
2022 Caterpillar Automatic Transfer Switch ATC Breaker / Contactor ATC-900 Controller

2022 Caterpillar Automatic Transfer Switch ATC Breaker / Contactor ATC-900 Controller

2022 Caterpillar Automatic Transfer Switch ATC Breaker / Contactor ATC-900 Controller

The ATC-900 Controller is a programmable microprocessor-based monitoring device for use on Cat transfer switches. Data access and programming operations are performed using the ATC-900's touch sensitive function buttons in conjunction with an easy-to-read illuminated alphanumeric LED display. Both the functional buttons and the display window are part of the device's door mounted front panel. A built in Help button provides user assistance in the form of message displays.

The communication option permits monitoring and control of several transfer switches, locally or remotely from a single point. Depending on the application, the user can customize the ATC-900 to meet the particular application. The ATC-900 is equipped to display historical information either via the front panel or over mod bus communications to a personal computer. Source 1 and Source 2 run time, available time and connect time are available, as well as load energized time, number of transfers, date, time and reason for the last 16 transfers.

THE ATC-900 IS A PROGRAMMABLE MICROPROCESSORBASED MONITORING DEVICE FOR USE ON CAT TRANSFER SWITCHES

IT IS A COMPACT AND SELF-CONTAINED PANEL-MOUNTED DEVICE THAT IS DESIGNED TO REPLACE TRADITIONAL RELAY AND SOLID-STATE LOGIC PANELS

features May Include:
  • true Rms Three-phase Voltage Sensing On Source 1, Source 2 And Load
  • frequency Sensing On Source 1 And Source 2
  • preferred Source Selection
  • programmable Set Points Stored In Nonvolatile Memory
  • modbus Communication To Personal Computer Either On Site Or Remote
  • viewable Historical Data On The Most Recent Transfers (Up To 16 Events) Are Viewable At Switch. Unlimited History Storage (Remote) Available When Used With Remote Software
  • engine Start Contacts (2 Sets)
  • engine Test Switch With User-selectable Test Mode And Fail-safe
  • alarm Contact (Multiple Alarm Functions Available)
  • heartbeat Monitor (Flashing Light Signifies That The Atc-800 Is Operating Properly)
instrumentation:
  • voltmeter (Accuracy ±1%)
  • reads Line-to-line On Sources 1 And 2 And Load
  • frequency Meter (40–80 Hz, Accuracy ±0.1 Hz)
  • source Available Time (Both Sources)

Electric

Electrical Rating Range: 120 to 600V, single phase and three phase @ 50/60 Hz | Input Control Voltage: 120Vac (50/60 Hz) (operating range 65 to 160 Vac) | Voltage Measurement Range: 0 to 700 Vac | Voltage Measurement Accuracy: +/-1% of full scale | Frequency Measurement Range: 40 Hz to 80 Hz | Frequency Measurement Accuracy: +/- 0.1 Hz | Undervoltage Dropout: Breaker Style 50 to 97% of Nominal System Voltage Contactor Style - 78 to 97% | Undervoltage Pickup: (Dropout +2%) to 99% of Nominal System Voltage | Underfrequency Dropout Range: 90 to 97% of Nominal System Frequency | Underfrequency Pickup Range: (Dropout +1 Hz) to 99% of Nominal System Frequency | Overfrequency Dropout Range: 103 to 110% of Nominal System Frequency | Overfrequency Pickup Range: 101% to (Dropout +1 Hz) of nominal system frequency | System Voltage Application: 120 to 600 Vac (50/60 Hz) (single or three phase)

Operational

Operating Conditions Humidity: Up to 90% Relative Humidity (non-condensing)
Operating Temperature, Maximum Range: -20 to 70 degree C (-4 to +158 degree F)

Features

Features Transfer Type: Switch application dependent | Switch Type: Switch application dependent | Voltage Measurements of Utility: Source 1, Source 2 and Load (VAB, VBC, VCA for Three Phase System) | Frequency Measurements Of: Source 1 and Source 2 | Enclosure Compatibility: NEMA 12 (std mounting) / NEMA 3R / UV Resistant Faceplate

Product Photography