E-W Truck & Equipment Co., Inc.

  • 6336 Federal Blvd.
  • San Diego, CA 92114
  • Call Us: (619) 263-2111
  • https://www.ewtruck.com/
Print This Page

2022 Caterpillar Mobile Generator Sets XQP150

Information

2022 Caterpillar Mobile Generator Sets XQP150

This XQP150 generator set is EU Stage IIIA emission standard capable or fuel consumption optimized for customers in non-regulated territories. Each model delivers increased flexibility by easily switching between 50 and 60 Hz, which allows one machine to satisfy varying load requirements across diverse regions and applications including mining, manufacturing, oil and gas and construction.

STANDARD 500 HOUR OIL CHANGE INTERVALS

Maximizes run time before routine service is required

FLEXIBLE 3-WAY FUEL VALVE

Extended run time provided by changeover from base tank to external bulk tank

SELECTABLE 50/60HZ OPERATION

Easy frequency switch via terminal link eliminate geographical limitations allowing generator set to be used wherever it is needed

Features may include:

  • Rental ready
  • Fuel/Emissions Strategy
  • Cat C7.1 Diesel Engine
  • Cat EMCP 4.2B Control Panel
  • Cat LC3114J Generator
  • Robust Galvanised Enclosure
  • Sound Isolated Operator Panel
  • Cat Connect
  • Factory Designed, Built and Tested
  • World Wide Product Support
  • 500 hr Oil Change Intervals
  • Improved Transportability
  • Additional Options Available

Photos

Highlights

  • San Diego, California
  • 2022
  • Caterpillar
  • Mobile Generator Sets XQP150
  • Model: C7.1 Diesel Engine or C7.1 ACERT Diesel Engine
  • Diesel
  • Available
  • 44.1 in
  • 87.6 in

Specifications

  • 2022
  • Caterpillar
  • Mobile Generator Sets
  • XQP150
  • General
  • Model: C7.1 Diesel Engine or C7.1 ACERT Diesel Engine
  • Diesel
  • Rating Prime: 150 kVA | Frequency: 50/60 Hz | Voltage: 127 - 480 V
  • Fuel Consumption EU Stage IIIA: 100% Load 50Hz - 9.9 gal/hr / 100% Load 60Hz - 11.2 gal/hr / 75% Load 50Hz - 7.8 gal/hr / 75% Load 60Hz - 9.2 gal/hr / 50% Load 50Hz - 5.4 gal/hr / 50% Load 60Hz - 6.3 gal/hr | Fuel Consumption Best Fuel Efficiency: 100% Load 50Hz - 8.8 gal/hr / 100% Load 60Hz - 10.5 gal/hr / 75% Load 50Hz - 6.5 gal/hr / 75% Load 60Hz - 7.7 gal/hr / 50% Load 50Hz - 4.3 gal/hr / 50% Load 60Hz - 5 gal/hr
  • EU Stage IIIA: Sound Power @ 1 meters (3 feet) @ 75% of rating (50Hz) - 73.1 dB(A) / Sound Power @ 1 meters (3 feet) @ 75% of rating (60Hz) - 76.4 dB(A) | Best Fuel Efficiency: Sound Power @ 1 meters (3 feet) @ 75% of rating (50Hz) - 74.7 dB(A) | Sound Power @ 1 meters (3 feet) @ 75% of rating (60Hz) - 78.3 dB(A)
  • 87.6 in
  • 138.6 in
  • 44.1 in
  • With Lube Oil and Coolant: 5615 lb